点击放大查看
8540300000
| Manufacturer | |
| Description | Signal Converter/Disconnector 12-Pin CONDITIONER SIGNAL DINRAIL MNT |
| Category |
对参数有疑问?问 AI 助手
Business
| Other Names | WAZ5 VCC 0-10V/4-20M | Standard Package | Bulk |
Compliance
| RoHS | Lead free / RoHS Compliant | Standards | DIN EN 50178, DIN EN 61000-4-2 |
| IEC Standard | 27-21-01-20 | IEC 61000-4-2 | EN 55011, EN 61000-6 |
| Standard Number | 31-12-10-07 | Declaration of Conformity | Declaration of Conformity |
Electrical
| Accuracy | 0.2 % | Frequency | 27-21-01-20 |
| Isolation | 3-way isolator | Range deg/s | 0.5 mm² |
| Load Current | ≤ 600 Ω | Response Time | ≤ 45 ms |
| Voltage Rating | 0...10 V | Current - Carry | ≤ 2 A |
| Current - Output | 4...20 mA | Number of Inputs | 1 |
| Voltage - Supply | 24 V DC ± 25 % | Number of Outputs | 1 |
| Resistance - Input | typ. 100 kΩ | Voltage - Breakdown | 2 kVeff / 5 s |
| Frequency - Output 3 | 10 Hz | Ratio - Input:Output | 0...10 V/ 4...20 mA |
| Voltage - Input (Min) | 4 kVeff / 1 min. | Power - Average Forward | < 1.5 W @ IOUT = 20 mA |
| Voltage - Output Supply | 2 kVeff / 5 s | Impulse Discharge Current (8/20us) | 4 kV |
Mechanical
| Depth | 112.4 mm | Width | 17.5 mm |
| Length | 92.4 mm | Weight | 101.1 g |
| Connector Type | Tension clamp connection | Depth (Inches) | 4.425 inch |
| Mounting Rails | TS 35 | Width (Inches) | 0.689 inch |
| Length (Inches) | 3.638 inch | Package Quantity | instruction sheet.pdf |
| Stripping Length | 7 mm | ||
Product Info
| Type | WAZ5 VCC 0-10V/4-20MA | Series | * |
| ETIM 6*0 | EC002653 | GTIN (EAN) | 4032248180684 |
| Description | Cross-connectors for power supplies and markers: refer to accessories | Configuration | none |
| Specifications | Standard signal isolating converter1-channel signal isolating converter in 17.5 mm width, with external power supply,to transmit and isolate analogue DC current signals from 0 to 10 VAdd-on housing for TS35 rail mountingDimensions: L/W/H 92.4/ 17.5/ 112.4 mmTension-clamp connection / Nominal cross-section 1.5 mm2Protection degree: IP 20 Input 0...10 VOutput 4...20 mATransmission error < 0,2% v. E. Limit frequency 10 HzAuxiliary power 24 VDC +/- 25 %Power loss approx. 1.3 WAmbient temperature range 0 °C...+55 °CSecure isolation EN 50178, 3-way isolation up to 4 kV AC/DC of all circuits against each otherTest voltage 4 kV input against output against auxiliary powerRated voltage 300 V AC/DC at overvoltage category III and pollution degree 2Approvals cULusType WAZ5 VCC 0-10/4-20MA | Engineering Data | EPLAN |
| Firmware Version | Signal converter/insulator, Tension clamp connection | Other Specifications | III |
Environmental
| Distance | ≥ 3 mm | ET (Volt-Time) | EC001774 |
| Ingress Protection | 2 | Operating Temperature | 0 to 55 °C |
| Temperature Coefficient | ± 250 ppm/K | ||
Documents & Media
PDF Document