点击放大查看
XCSDMP5912
| Manufacturer | |
| Description | Non-contact safety switch,1NO/1NC,LED Magnetic / Reed Switches Safety inter, mag, rect, 2m cable Schneider Electric component XCSDMP5912: coded magnetic switch XCSDMP - SIL 3 - 1 NC+1 NO, NC staggered - cable 2 m |
| Category |
对参数有疑问?问 AI 助手
Business
| Lead Time | 14 Days | Subcategory | Switch Safety Interlock |
Compliance
| RoHS | Compliant | Standards | CSA C22-2 No 14EN 1088EN/IEC 60204-1EN/IEC 60947-5-1EN/ISO 12100ISO 14119UL 508 |
| Protection | Class II conforming to IEC 60536 | Certification | BGCSAUL |
| Safety Category | B10d = 5000000 (value given for a life time of 20 years limited by mechanical or contact wear) | ||
Electrical
| Resistance | 57 Ohm | Sensitivity | >= 0.3 mT |
| Voltage - UL | 24 V DC | Voltage Rating | 100 V DC |
| Number of Poles | 2 | Sensing Distance | 20 mm |
| Voltage - Supply | 24 V dc | Switching Voltage | 100 V DC |
| Current - Switching | 5...100 mA | Current Rating (Max) | <= 100 A |
| Frequency - Switching | 150 Hz | Insulation Resistance | 1000 MOhm |
| Voltage - Supply (Min) | <= 3 VA | Voltage - Breakdown (V(BR)GSS) | 2.5 kV conforming to EN/IEC 60947-5-1 |
| Current - Short Circuit Rating (SCCR) | 500 mA external cartridge fuse type gG (gl) | ||
Mechanical
| Depth | 13mm | Width | 25mm |
| Length | 88mm | Weight | 0.18 kg |
| Material | Plastic | Cable Length | 2 m |
| Cable Material | PVC | Connector Type | Pre-cabled |
| Contact Timing | Staggered | Contact Material | Rhodium |
| Housing Material | Thermoplastic PBT | Size / Dimension | 88 x 25 x 13 mm |
| Supplier Device Package | XCSDMP | Exterior Housing Material | Thermoplastic PBT |
Product Info
| Design | Rectangular, standard | Direction | 3 directions |
| Switch Type | Saftey | Product Type | Coded magnetic switch |
| Electrical Life | 1200000 cycles | Measuring Range | Preventa Safety detection |
| Industry Aliases | 3389119113045 | Other Specifications | 1 LED |
Environmental
| Seal Rating | IP66, IP67 | Shock Resistance | 30 gn for 11 ms conforming to IEC 60068-2-27 |
| Storage Interface | -40...85 °C | Ingress Protection | IP66 conforming to IEC 60529IP67 conforming to IEC 60529 |
| Operating Pressure | 8 mm | Protective Treatment | TH |
| Vibration Resistance | 10 gn (f = 10...150 Hz) conforming to IEC 60068-2-6 | Operating Temperature | -25...85 °C |