点击放大查看
NSYCU760W230VL
| Manufacturer | |
| Description | Cooling Unit 760W 230V SideMount Schneider Electric component NSYCU760W230VL: Climasys Cooling Unit, 760W, 230V, lateral mounting Ral 7035 |
| Category |
对参数有疑问?问 AI 助手
Compliance
| Protection | Thermal protection: T 3 A | ||
Electrical
| Noise | 67 dB | Current | 7.7 A8.8 A |
| Efficiency | 2 1.8 | Filter Type | External circuit |
| Output Type | Alarm output inverter contact | Power - Rated | 760 W 50 Hz L35-L35810 W 60 Hz L35-L35610 W 50 Hz L35-L50640 W 60 Hz L35-L50 |
| Voltage Rating | 230 V 50/60 Hz | Current Rating (Max) | 2 A2.3 A |
| No Load Power Consumption | 380 W 50 Hz L35-L35440 W 60 Hz L35-L35440 W 50 Hz L35-L50500 W 60 Hz L35-L50 | ||
Mechanical
| Color | Grey RAL 7035 | Depth | 195 mm |
| Width | 350 mm | Height | 800 mm |
| Weight | 33 kg | Air Flow | Internal circuit: 350 m3/h at 50 HzInternal circuit: 385 m3/h at 60 HzExternal circuit: 350 m3/h at 50 HzExternal circuit: 385 m3/h at 60 Hz |
| Material | Steel | Mounting Type | Side |
Product Info
| Product Type | Cooling unit | Control Method | Thermostat |
| Measuring Range | ClimaSys CU | ||
Environmental
| Cooling Type | R134a (0.5 kg) | Temperature Range | 20...50 °C |
| Ingress Protection | IP54 on the internal circuit conforming to IEC 60529IP34 on the external circuit conforming to IEC 60529 | Operating Temperature | <= 55 °C outside |