点击放大查看
LU2B32ES
| Manufacturer | |
| Description | Controllers 32A SELF-PR.REV.STR W/TERMS- LUC*ES Schneider Electric component LU2B32ES: power base - TeSys U - 32 A - 48...72 V DC screw clamps control |
| Category |
对参数有疑问?问 AI 助手
Business
| Lead Time | 14 Days | Subcategory | Solid State Relay |
Compliance
| Standards | CSA C22-2 No 14 type EEN 60947-6-2IEC 60947-6-2UL 508 type E with phase barrier | Certification | ABSASEFAATEXBVCCCCSADNVGLGOSTLROS (Lloyds register of shipping)UL |
Electrical
| Circuit | 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N | Frequency | 40...60 Hz |
| Isolation | Yes | Voltage - UL | 230 V440 V500 V690 V |
| Voltage - I/O | 70 % 500 ms conforming to IEC 61000-4-11 | Voltage Rating | 600 V conforming to CSA C22-2 No 14600 V conforming to UL 508690 V conforming to IEC 60947-1 3 |
| Number of Poles | 3P | Current - Output | 280 mA at 48...72 V AC I maximum while closing280 mA at 48...72 V DC I maximum while closing35 mA at 48...72 V AC I rms sealed35 mA at 48...72 V DC I rms sealed |
| Voltage - Supply | 29 V 48 V AC drop-out29 V 48...72 V DC drop-out38.5...72 V 48 V AC in operation38.5...93 V 48...72 V DC in operation | Current Rating (Max) | 21 A at 690 V23 A at 500 V32 A at <= 440 V |
| Frequency - Operating | 60 cyc/mn | Voltage - Supply (Min) | 10 kA 500 V4 kA 690 V50 kA 230 V50 kA 440 V |
| Power Dissipation (Max) | 3 W for control circuit with LUCA, LUCB, LUCC, LUCD1.8 W for control circuit with LUCM | Voltage - Breakdown (V(BR)GSS) | 6 kV conforming to IEC 60947-6-2 |
| Impedance - Unbalanced/Balanced | 10 V/m 3 conforming to IEC 61000-4-3 | Resistance - Wiper (Ohms) (Typ) | 8 kV level 3 in open air conforming to IEC 61000-4-28 kV level 4 on contact conforming to IEC 61000-4-2 |
| ESR (Equivalent Series Resistance) | 2 kV class 3 serial link conforming to IEC 61000-4-44 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 | Common Mode Transient Immunity (Min) | 3 ms |
Mechanical
| Depth | 126 mm | Width | 45 mm |
| Height | 224 mm | Weight | 1.27 kg |
| Contact Type | Type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1Type mirror contact (1 NC) state of the power conforming to draft IEC 60947-1 | 1st Connector | Control circuit: screw clamp terminals 1 cable 0.34...1.5 mm ² - cable stiffness: flexible - with cable endControl circuit: screw clamp terminals 1 cable 0.75...1.5 mm ² - cable stiffness: flexible - without cable endControl circuit: screw clamp terminals 1 cable 0.75...1.5 mm ² - cable stiffness: rigid - without cable endControl circuit: screw clamp terminals 2 cable 0.34...1.5 mm ² - cable stiffness: flexible - with cable endControl circuit: screw clamp terminals 2 cable 0.75...1.5 mm ² - cable stiffness: flexible - without cable endControl circuit: screw clamp terminals 2 cable 0.75...1.5 mm ² - cable stiffness: rigid - without cable endPower circuit: screw clamp terminals 1 cable 1...10 mm ² - cable stiffness: rigid - without cable endPower circuit: screw clamp terminals 1 cable 1...6 mm ² - cable stiffness: flexible - with cable endPower circuit: screw clamp terminals 1 cable 2.5...10 mm ² - cable stiffness: flexible - without cable endPower circuit: screw clamp terminals 2 cable 1...6 mm ² - cable stiffness: flexible - with cable endPower circuit: screw clamp terminals 2 cable 1...6 mm ² - cable stiffness: rigid - without cable endPower circuit: screw clamp terminals 2 cable 1.5...6 mm ² - cable stiffness: flexible - without cable end |
| Dielectric Diameter | 10 V conforming to IEC 61000-4-6 | Torque - Max Momentary (oz-in / mNm) | Control circuit: 0.8...1.2 N.m - with screwdriver 5 mm flatControl circuit: 0.8...1.2 N.m - with screwdriver 5 mm Philips no 1Power circuit: 1.9...2.5 N.m - with screwdriver 6 mm flatPower circuit: 1.9...2.5 N.m - with screwdriver 6 mm Philips No 2 |
Product Info
| Usage | AC-41AC-43AC-44 | Duration | 15 ms for DC network25 ms for AC network 50/60 Hz |
| Composition | 2 NO | Product Type | Reversing power base |
| Measuring Range | TeSys U | Rechargeability | 1369863 cycles20000000 cycles |
| Industry Aliases | 785901202578, LU2B32ES | Device Short Name | LU2B |
| Other Specifications | 650 °C conforming to IEC 60695-2-12960 °C parts supporting live components conforming to IEC 60695-2-12 | ||
Environmental
| Operate Time | 150 ms with change of direction for power circuit35 ms opening for control circuit60 ms closing for control circuit75 ms without change of direction for power circuit | Mechanical Life | 15000000 cycles |
| Shock Resistance | 10 gn power poles open conforming to IEC 60068-2-2715 gn power poles closed conforming to IEC 60068-2-27 | Storage Interface | -40...85 °C |
| Ingress Protection | IP20 front panel and wired terminals conforming to IEC 60947-1IP20 other faces conforming to IEC 60947-1IP40 front panel outside connection zone conforming to IEC 60947-1 | Operating Pressure | 2000 m |
| Protective Treatment | TH conforming to IEC 60068 | Vibration Resistance | 2 gn 5...300 Hz power poles open conforming to IEC 60068-2-274 gn 5...300 Hz power poles closed conforming to IEC 60068-2-27 |
| Operating Temperature | -25...60 °C with LUCM-25...70 °C with LUCA, LUCB, LUCC, LUCD | Thermal Current (Ith) | 32 A |