点击放大查看
GVAN113
| Manufacturer | |
| Description | Industrial Relays MAN-START AUX CONTACT 575VAC 1AMP Schneider Electric component GVAN113: TeSys GV2 & GV3 - auxiliary contact block - 1 NO + 1 NC Circuit Breakers MAN-START AUX CONTACT 575VAC 1AMP |
| Category |
对参数有疑问?问 AI 助手
Business
| Lead Time | 14 Days | Subcategory | Circuit Protection Misc |
Compliance
| Protection | GB2CB... circuit breaker rating according to operational current for Ue <= 415 VGG fuse <= 10 A | ||
Electrical
| Voltage - UL | 48...690 V AC24...240 V DC | Power - Rated | 300 VA at 48 V AC-15 - electrical durability: 100000 cycles400 VA at 690 V AC-15 - electrical durability: 100000 cycles500 VA at 110...127 V AC-15 - electrical durability: 100000 cycles500 VA at 500 V AC-15 - electrical durability: 100000 cycles650 VA at 440 V AC-15 - electrical durability: 100000 cycles720 VA at 230...240 V AC-15 - electrical durability: 100000 cycles850 VA at 380...415 V AC-15 - electrical durability: 100000 cycles |
| Voltage Rating | 600 V - conforming to CSA C22-2 No 14600 V - conforming to UL 508690 V - conforming to IEC 60947-1 | Switching Voltage | 17 V |
| Current - Switching | 5 mA | Power (Watts) - Max | 120 W at 240 V DC-13 - electrical durability: 100000 cycles140 W at 110 V DC-13 - electrical durability: 100000 cycles140 W at 24 V DC-13 - electrical durability: 100000 cycles180 W at 60 V DC-13 - electrical durability: 100000 cycles240 W at 48 V DC-13 - electrical durability: 100000 cycles |
Mechanical
| Depth | 66 mm | Width | 9.3 mm |
| Height | 89 mm | Weight | 0.06 kg |
| 1st Connector | Control circuit: spring terminals 1 cable 0.75...2.5 mm ² - cable stiffness: flexible - without cable endControl circuit: spring terminals 2 cable 0.75...2.5 mm ² - cable stiffness: flexible - without cable end | Mounting Type | Left side |
| Mounting Style | DIN Rail | Contact Material | 1 NO + 1 NC |
Product Info
| Manufacturer | Schneider Electric | Product Type | Auxiliary contact block |
| Compatibility | GV2LGV2LEGV2MEGV2PGV2RTGV3LGV3P | Measuring Range | TeSys GV2TeSys GV3 |
| Industry Aliases | 785901494911, GVAN113 | Device Short Name | GVAN |
Environmental
| Ingress Protection | Normal environment | Thermal Current (Ith) | 6 A |