点击放大查看
GV7RS50
| Manufacturer | |
| Description | Motor Circuit Breaker GV7RS50 Motor Drives MAN-START 600VAC 50AMP IEC Schneider Electric component GV7RS50: motor circuit breaker GV7-RS - 3 poles 3d - 30...50 A - thermomagnetic trip unit Schneider Electric TeSys GV GV7R 系列 30 → 50 A 3极 电动机保护断路器 , 10 kA断开能力, 690 V |
| Category |
对参数有疑问?问 AI 助手
Business
| Lead Time | 14 Days | Subcategory | Circuit Protection Misc |
Compliance
| RoHS | Compliant | Standards | EN 60947-1EN 60947-2EN 60947-4-1IEC 60947-1IEC 60947-2IEC 60947-4-1NF C 63-120NF C 63-650NF C 79-130VDE 0113VDE 0660 |
| Certification | CCCDNVUL | ||
Electrical
| Frequency | 50/60 Hz conforming to CSA50/60 Hz conforming to IEC 60947-4-150/60 Hz conforming to UL | Isolation | Yes conforming to IEC 60947-1 § 7-1-6 |
| Duty Cycle | Yes conforming to IEC 60947-4-1 § 7-2-1-5-2 | Voltage - UL | 600 V AC 50/60 Hz conforming to CSA C22-2 No 14600 V AC 50/60 Hz conforming to UL 508690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Power - Output | 22 kW at 400...415 V AC 50/60 Hz30 kW at 500 V AC 50/60 Hz30 kW at 660...690 V AC 50/60 Hz | Voltage Rating | 690 V |
| Number of Poles | 3P | Duty Cycle (Max) | Continuous conforming to IEC 60947-4-1 |
| Voltage - Supply | 10 KA | Current Rating (Max) | 50 A |
| Resistance Tolerance | 0.5 J | Voltage - Supply (Min) | 10 KA |
| Power Dissipation (Max) | 5 W | Voltage - Breakdown (V(BR)GSS) | 8 kV conforming to IEC 60947-2 |
Mechanical
| Depth | 111mm | Width | 105mm |
| Height | 161 mm | Length | 161mm |
| Weight | 2.015 kg | 1st Connector | Power circuit: screw clamp terminal |
| Mounting Type | Fixed | Terminal Type | Screw Clamp |
| Connector Type | 螺钉 | Mounting Feature | HorizontalVertical |
| Size / Dimension | 161 x 105 x 111 mm | Pitch - Connector | 35 mm without spreaders45 mm with spreaders |
| Torque - Max Momentary (oz-in / mNm) | 10 N.m - on screw clamp terminal | ||
Product Info
| Type | Bars - width: <= 25 mm - height: 20 mm - distance hole to end: <= 10 - thickness: <= 6 mm - screw: M6Lugs - width: <= 25 mm - distance hole to end: <= 10 - thickness: <= 6 mm - screw: M6 | Usage | AC-3 conforming to IEC 60947-4-1Category A conforming to IEC 60947-2 |
| Series | GV7R | Control Method | Rocker lever |
| Electrical Life | 30000 cycles on AC-3 at 440 V In50000 cycles on AC-3 at 440 V In/2 | Measuring Range | GV7R |
| Number of Gangs | 25 cyc/h | Industry Aliases | 785901294351, GV7RS50 |
| Device Short Name | Thermal magnetic circuit breaker | Network Technology | AC |
| Other Specifications | 30 → 50 A | Application Specifics | Motor protection |
Environmental
| Mechanical Life | 50000 cycles | Shock Resistance | 15 gn 20 ms conforming to IEC 60068-2-27 |
| Storage Interface | -55...95 °C | Ingress Protection | IP405 open mounted conforming to IEC 60529IP405 with terminal shrouds conforming to IEC 60529 |
| Operating Pressure | <= 2000 m | Protective Treatment | TC |
| Vibration Resistance | 2.5 gn 25 Hz conforming to IEC 60068-2-6 | Operating Temperature | -25...70 °C open mounted |
| Thermal Current (Ith) | 50 A conforming to IEC 60947-4-1 | Thermal Resistance @ Natural | 30...50 A conforming to IEC 60947-4-1 |